Using the wrong fire extinguisher can spread a fire or electrocute the operator. Under NFPA 10 and OSHA 29 CFR 1910.157, every site must match extinguishers to the fuel classes present and inspect them monthly.
Matching Fire Classes to Extinguisher Types
| Extinguisher Type | Suitable Fire Classes | Never Use On |
|---|---|---|
| Water | Class A (wood, paper, textiles) | Electrical fires, flammable liquids, cooking oils |
| Foam (AFFF) | Class A and Class B (flammable liquids) | Live energized electrical equipment |
| Dry Chemical Powder (ABC) | Class A, B, and C / electrical | Sensitive electronics where residue causes severe damage (use CO2 instead) |
| Carbon Dioxide (CO2) | Class B and energized electrical equipment | Confined spaces without ventilation; never grip the frost-cold horn directly |
| Wet Chemical | Class K / F (deep-fat kitchen oils) | Energized electrical panels |
Using an Extinguisher Safely: The PASS Method
Fight only an incipient (early-stage) fire with an unobstructed exit behind your back:
- Pull the safety pin to break the tamper seal.
- Aim the nozzle low at the base of the flames, not the smoke.
- Squeeze the operating handle steadily.
- Sweep side to side across the base until the fire is out, then watch for re-ignition.
Monthly Inspection Points (NFPA 10)
Verify every unit monthly: unobstructed access, pressure gauge needle inside the green zone (or verified weight for CO2), intact pin and tamper seal, uncracked hose, and current annual maintenance tag.